E-Mon E-PS-E-RTU-N User Manual

Page 79

Advertising
background image

Chapter 5 Configuring the PowerSmart+ PQM

General Meter Setup

PowerSmart+ Power Quality Meter

79

Table 10: User-configurable Device Options

Parameter

Options

Default

Description

Power Calculation
Mode

Reac = using reactive
power S=f(P, Q),
Nact = using non-active
power Q=f(S, P)

S=f(P, Q) The method used for

calculating reactive and
apparent powers (see

Power

Calculation Modes

below)

Energy Roll Value

E, EH

10000 kWh
100000 kWh
1000000 kWh
10000000 kWh
100000000 kWh
1000000000 kWh

10000000 The value at which energy

counters roll over to zero

Phase Energy
Calculation

E, EH

Disabled
Enabled

Disabled

Enables phase energy
calculations

Energy Test Mode

E, EH

Disabled
Wh pulses
varh pulses

Disabled

Setting this option puts the
meter into the energy test
mode (see

Energy Pulse LED

in Chapter 3)

Starting Voltage

1.5-5.0%

1.5%

The device starting voltage in
percent of FS (120V or 400V)

Device Resolution

Low
High

Low

The voltage, current and
power resolution on the front
display (see

Measurement Units

in Chapter 3) and in
communications (see
communication guides)

Volts Scale, V

60-828 V

144 V

The maximum voltage scale
allowed, in secondary volts.
See

Data Scales

in Appendix F

Amps Scale, A

1.0-10.0 A

2 × CT
secondary

The maximum current scale
allowed, in secondary amps.
See

Data Scales

in Appendix F

Figure 5-7: General Setup Dialog Box – Device Options Tab

Advertising
This manual is related to the following products: