General Meter Setup

86

PowerSmart+ Power Quality Meter

based on measured analog and digital values that produce a required
action.

The meter provides 16 control setpoints with programmable operate and
release delays. Each setpoint evaluates a logical expression with one
trigger argument. Whenever an expression is evaluated as “true”, the
setpoint performs a programmable action that can send a command to the
output relay, or increment a counter.

The logical controller provides very fast response to events. The scan time
for all setpoints is 1 cycle time (16.6 ms at 60Hz and 20 ms at 50/400
Hz).

Using the Front Display

Select Setpoint Setup menu from the Device Setup menu to enter the
setup menu. See

Viewing and Changing Setup Options

in Chapter 3 for

information on configuring parameters via the front display.

Use the UP/DOWN buttons to scroll to the required setpoint.

To select a setpoint parameter:

1. Press SELECT/ENTER button to select required setpoint.

2. Use the UP/DOWN buttons to scroll to the required parameter.

To change the parameter value:

1. Press SELECT/ENTER button to enter the parameter options

menu.

2. Use the UP/DOWN buttons to select the required value.

3. Press SELECT/ENTER button to confirm the new setting

To store your new setpoint settings after you configured all
setpoint parameters:

1. SELECT Save Setup function from Setpoint Setup menu and press

SELECT/ENTER button to enter Save Setup menu

You are returned to the upper window and can select another
setpoint or exit the menu.

2. SELECT Save and press SELECT/ENTER button to Save Setpoint

parameters.