background image

Chapter 4 Power

S O F T W A R E

V I E W I N G R E C O R D E D F I L E S

PowerSmart+ Advanced Power Quality Meter

115

The standard compliance statistics is reported within the selected time range on a daily,
weekly or yearly basis depending on the observation periods stated in the EN50160 for
voltage characteristics. If the time range includes a number of the observation intervals,
each interval’s statistics is given in a separate row. For power frequency, both weekly and
yearly compliance statistics are provided.

For characteristics provided with definite limits, the report shows a percentage of the
observation time within which the characteristic complied with the standard, e.g. 98% of the
observations in a period of one week, and the total compliance indicator.

For voltage characteristics provided with indicative values, the report gives the yearly
statistical data classified by voltage magnitude and duration.

Selecting the Report Time Range

To change the time range or contents of the report, click on the report with the right mouse
button, select “Options…”, select the required time range, check the voltage characteristics
to be included in the report, and then click OK.

Customizing Reports

If you wish to add a logo image, header and footer to your reports: