Chapter 3 Display

O P E R A T I O N S

M E N U O P E R A T I O N S

48

PowerSmart+ Advanced Power Quality Meter

The following table lists available setpoint options. For a list of available setpoint
triggers and actions, see

Using Control Setpoints

in Chapter 4.

Label

Parameter

Options

Description

LGC.2-
LGC.4

Logical operator OR, AND

Combines setpoint triggers in a
logical expression

TrG.1-TrG.4 Trigger

parameter #1-
#4

See
Appendix C

The analog or digital value that is
used as an argument in a logical
expression

On.1-On.4

Operate limit

The threshold (in primary units) at
which the conditional expression
would be evaluated to true. Not
applicable for digital triggers.

OFF.1-
OFF.4

Release limit

The threshold (in primary units) at
which the conditional expression
would be evaluated to false. Defines
the hysteresis for analog triggers.
Not applicable for digital triggers.

Act.1-Act.4

Setpoint action
#1-#4

See
Appendix C

The action performed when the
setpoint expression is evaluated to
true (the setpoint is in operated
state)

On d

Operate delay

0-999.9 sec The time delay before operation

when the operate conditions are
fulfilled

OFF d

Release delay

0-999.9 sec The time delay before release when

the release conditions are fulfilled

Analog Inputs Setup

Analog Inputs Setup

Analog Inputs Setup

Analog Inputs Setup

This entry appears only if the meter is ordered with optional analog inputs. For more
information on configuring analog inputs in your meter, see

Programming Analog

Inputs

in Chapter 4.

To enter the menu, select the “A.In.1” or “A.In.2” entry from the main menu for the
AI1 and AI2 inputs respectively, and press the ENTER button.

To change the analog input options:

Use the UP and DOWN arrow buttons to scroll to the desired parameter.

Press the SELECT button to activate the lower window.

Use the UP and DOWN arrow buttons to adjust the parameter value.

Press ENTER to confirm the new parameter setting, or press ESC to discard changes.

You are returned to the middle window to select another parameter, or store your new
settings and exit the menu.

To store new settings and exit the menu:

When the middle window is highlighted, press the ENTER button.

You return to the Main menu.

To exit the menu without saving your changes, press ESC.

The following table lists available analog input options.

SEtP

rEL.1

Act.1

SP.1

180

OFF.

A.In.

ESC

A.In.1

0

Lo

A.In.1

Hi

A.In.1

1

dEc.P