Status display – E-Mon E-PS-A-RTU-N User Manual

Page 39

Advertising
background image

Chapter 3 Display

O P E R A T I O N S

S T A T U S D I S P L A Y

PowerSmart+ Advanced Power Quality Meter

39

TOU Energy Register 8

8



rEG.8
trF.8
MWh

Tariff 8 reading

Status Display

The meter has separate status information pages accessible through the primary
device menu. The Status Display shows rarely used information that is especially
helpful when connecting the meter inputs and outputs to external equipment. For
information on navigating in the menus, see

Using the Menus

.

To enter the Status Display:

From the Data Display, press the SELECT button to enter the primary device menu. The
“StA” window is highlighted.

Press ENTER to enter the Status Display. Use the UP and DOWN arrow buttons to
scroll through the status pages.

To exit the Status Display:

Press ESC to return to the primary device menu.

Press ESC to return to the Data display.

Status Display

1



PhS
rot
POS/nEG/Err

Phase rotation order

2



AG.

V1 angle
V2 angle
V3 angle

Voltage angles (±180°, referenced to
V1)

3



AG.

I1 angle
I2 angle
I3 angle

Current angles (±180°, referenced to
V1)

4



rEL
1.2.
00

Relay status

5



St.In
1.2.
00

Status inputs

6



Cnt.1

Counter #1

7



Cnt.2

Counter #2

8



Cnt.3

Counter #3

9



Cnt.4

Counter #4

10



batt

nor/Lo

Backup battery status (Normal/Low)

ENERG

Y

StA

CHG

OPS

SELECT

ENERG

Y

Advertising
This manual is related to the following products: