Menu operations, Basic device settings – E-Mon E-PS-A-RTU-N User Manual

Page 42

Advertising
background image

Chapter 3 Display

O P E R A T I O N S

M E N U O P E R A T I O N S

42

PowerSmart+ Advanced Power Quality Meter

If a number represents the parameter, adjust it to the desired value with the UP and DOWN
arrow buttons. When briefly pressed, the button increments or decrements the number by
one. When the button is pressed continuously, the number is changed approximately twice
per second.

If a name represents the parameter, select the desired option with the UP and DOWN
arrow buttons.

To store your new selection, press the ENTER button.

To leave the parameter unchanged, press the ESC button.

You will return to the parameter list to select another parameter or return to the main
menu.

To exit the menu, press ESC.

Menu Operations

Basic Device Settings

Basic Device Settings

Basic Device Settings

Basic Device Settings

This menu allows you to configure the basic meter settings that define the general
operating characteristics of the device. To enter the menu, select the “baSc” entry
from the main menu, and then press the ENTER button.

To select a setup option:

Press the SELECT button to activate the middle window.

Use the UP and DOWN arrow buttons to scroll to the desired option.

To change the option:

Press the SELECT button to activate the lower window.

Use the UP and DOWN arrow buttons to select the desired option.

Press ENTER to confirm your changes and to store your new setting, or press ESC to
discard changes.

To exit the menu, press ESC.

The following table lists available options.

Label

Parameter

Options

Default

Description

ConF

Wiring connection
(configuration) mode

See “Basic
Meter
Setup” in
Chapter 4

4Ln3

The wiring connection of the
device

Pt

PT ratio

1.0-6500.0

1.0

The phase potential
transformer’s primary to
secondary ratio

Pt.F

PT Ratio multiplier

Ч1, Ч10

Ч1

PT Ratio multiplication factor.
Used in extra high voltage
networks to accommodate the
PT ratio for 500 kV and higher
networks.

U.SEC

Nominal secondary
voltage

10-690 V

120 V

The nominal secondary line-to-
neutral (in 4LN3, 3LN3 and
3BLN3 wiring modes) or line-to-
line (in 4LL3, 3LL3, 3BLL3,
3OP2, 3OP3 and 3DIR modes)
voltage. Used as a reference
voltage for the EN50160
evaluation.

bASc

4Ln3

ConF

bASc

1.0

Pt

bASc

200.0

Pt

ENERGY

ENTER

SELECT

bASc

200.0

Pt

THD/TDD

ESC