Chapter 3 Display

O P E R A T I O N S

D A T A D I S P L A Y

34

PowerSmart+ Advanced Power Quality Meter

Phase Power Readings

In configurations with the neutral wire, in addition to total three-phase powers, the meter
can show per-phase power readings. By default, they are disabled. See

Display Setup

on

how to enable per-phase power readings in your meter.

Fundamental Component

The meter can display total power factor and active power for the fundamental
component if it is enabled through the Display Setup menu. Whenever phase power
readings are allowed, the PowerSmart+ Advanced PQM also displays per-phase
power factor and active power for the fundamental component.

Auto Return

If no buttons are pressed for 30 seconds while the display Auto Return option is
enabled, the display automatically returns to the main screen from any other
measurement display or programming mode.

The Auto Return option can be enabled through the Display Setup menu

Auto Scroll

If no buttons are pressed for 30 seconds while in the common measurements
display, and the Auto Scroll option is enabled in the meter, the display automatically
scrolls through all available pages. The scroll interval can be adjusted through the
Display Setup menu.

To stop auto scrolling, press briefly the UP or DOWN button.

Navigation Buttons

Navigation Buttons

Navigation Buttons

Navigation Buttons

In Data Display mode, the navigation buttons function as follows.

The MI

MI

MI

MIN/MAX

N/MAX

N/MAX

N/MAX button switches to the Min/Max - Maximum Demands display pages.

When briefly pressed again, it switches back to the common measurements display.

The PQ

PQ

PQ

PQ button switches between different power quality/harmonic displays: Total

Harmonics, Individual Voltage and Current Harmonics, and Power Quality
parameters – short-term (Pst) and long-term (Plt) flicker, and voltage and current
negative sequence unbalance. When briefly pressed once again, it switches back to
the common measurements display

The UP

UP

UP

UP and D

D

D

DOWN

OWN

OWN

OWN arrow buttons, labeled by arrowheads, scroll forwards and

backwards through the display pages. Pressed briefly, they move one page forward
or backward. If you hold down the button the display pages are scrolled at rate of a
twice per second.

Pressing both the UP and DOWN arrow buttons together returns to the first page
within the current display.

The SELECT

SELECT

SELECT

SELECT button operates once it’s released. The button has two functions:

When pressed briefly, it switches to programming mode.

When pressed together with the ENTER button for more than 5

seconds, it resets Min/Max records, maximum demands, or
energies depending on the currently displayed page. If the meter
is password protected, and a simple reset of data from the
display is not allowed, the action has no effect.

The ENERGY

ENERGY

ENERGY

ENERGY button switches to the Energy display. If TOU registers are configured in the

meter, you can repeatedly press this button to scroll through all available TOU registers.
When briefly pressed once again, it switches back to the common measurements display

ENERGY

ENTER

PQ

ESC

MIN

MAX

SELECT

Advertising