Control setpoint setup – E-Mon E-PS-A-RTU-N User Manual

Page 47

Advertising
background image

Chapter 3 Display

O P E R A T I O N S

M E N U O P E R A T I O N S

PowerSmart+ Advanced Power Quality Meter

47

Use the UP and DOWN arrow buttons to enter the desired multiplier.

Press ENTER to confirm your changes and to store the new settings, or press ESC to
discard changes.

You are returned to the upper window to select another counter or exit the menu.

To exit the menu, press ESC.

The following table lists available counter options.

Parameter

Options

Default Description

Pulse source

None = disabled

Inp.1 = DI1
Inp.2 = DI2

None

Links a digital input to the counter

Multiplier

1-9999

1

The value added to the counter
when a pulse is detected on the
pulse source input, or the counter is
incremented through a setpoint
action

Control Setpoint Setup

Control Setpoint Setup

Control Setpoint Setup

Control Setpoint Setup

The PowerSmart+ Advanced PQM provides 16 control setpoints with programmable
operate and release delays. Each setpoint evaluates a logical expression with up to four
arguments using OR/AND logic. Whenever an expression is evaluated as “true”, the
setpoint performs up to four concurrent actions that can send a command to the output
relays, increment or decrement a counter, or trigger a recorder. For more information on
setpoints operation, see

Using Control Setpoints

in Chapter 4.

This menu configures setpoints through the front display. To enter the menu, select
the “SEtP” entry from the main menu, and press the ENTER button.

The menu uses three entries:

The upper window indicates a setpoint number.

The middle window selects a setup parameter to view or change.

The lower window displays the parameter value.

Use the UP and DOWN arrow buttons to scroll to the desired setpoint.

To select a setpoint parameter:

Press the SELECT button to activate the middle window.

Use the UP and DOWN arrow buttons to scroll to the desired parameter.

To change the parameter value:

Press the SELECT button to activate the lower window.

Use the UP and DOWN arrow buttons to select the desired value.

Press ENTER to confirm the new parameter setting, or press ESC to discard changes.

You are returned to the middle window to select and configure another parameter, or
confirm the setpoint settings and exit the menu.

To store your new setpoint settings after you configured all setpoint parameters:

When the middle window is highlighted, press the ENTER button.

You are returned to the upper window to select another setpoint or exit the menu.

To exit the menu, press ESC.

SP.1

rtHi.C

1

trG.1

SP.1

200

On.1

SEtP

ESC

SP.1

180

OFF.

1

SP.1

Or

LOG.

2

SP.1

rtHi.C

2

trG.2

SP.1

200

On.2

Advertising
This manual is related to the following products: