Configuring communication protocols, Configuring modbus, Modbus point mapping – E-Mon E-PS-A-RTU-N User Manual

Page 97

Advertising
background image

Chapter 4 Power

S O F T W A R E

C O N F I G U R I N G C O M M U N I C A T I O N

P R O T O C O L S

PowerSmart+ Advanced Power Quality Meter

97

Option

Range

Default

Description

Rapid Voltage Changes

Repetition Rate 1-10

1

Defines the maximum repetition rate in variations
per hour (equal or less than) for rapid voltage
changes. Voltage changes at higher rates are not
classified since they will be subject for flicker.

Flicker

Pst Period

1-10 min

10 min

Defines the period of time for the short-term
flicker evaluation. The standard setting of 10
minutes can be temporarily changed in the device
for testing purposes.

Harmonic Voltage

THD, up to
order

25-50

40

Defines the highest harmonic order included in
the THD evaluation.

Harmonics, up
to order

25-50

25

Defines the highest harmonic order for evaluation
of the harmonic voltages.

Interharmonic Voltage

Evaluation

Disabled,
Enabled

Disabled

Enables the evaluation of the interharmonic
voltages

THD, up to
order

25-50

40

Defines the highest interharmonic order included
in the THD evaluation.

Interharmonics,
up to order

25-50

25

Defines the highest harmonic order for evaluation
of the interharmonic voltages.

Mains Signaling Voltage

Evaluation

Disabled,
Enabled

Disabled

Enables the evaluation of the mains signaling
voltages

1st Signaling
Frequency

110-3000
Hz

183.0 Hz

Specifies the mains signaling frequency for the
compliance evaluation

2nd Signaling
Frequency

110-3000
Hz

191.0 Hz

Specifies the mains signaling frequency for the
compliance evaluation

3rd Signaling
Frequency

110-3000
Hz

217.0 Hz

Specifies the mains signaling frequency for the
compliance evaluation

4th Signaling
Frequency

110-3000
Hz

317.0 Hz

Specifies the mains signaling frequency for the
compliance evaluation

Clearing EN50160 Evaluation Counter

Clearing EN50160 Evaluation Counter

Clearing EN50160 Evaluation Counter

Clearing EN50160 Evaluation Counterssss

To clear the present contents of the EN50160 evaluation counters before starting your
EN50160 evaluation, check the On-line button, select Reset from the Monitor menu, and
then Click on the “Clear EN50160 Counters” button (for more information, see

Resetting

Accumulators and Clearing Log Files

).

Configuring Communication Protocols

This section describes how to customize protocol options for use with your application
software.

Configuring Modbus

Configuring Modbus

Configuring Modbus

Configuring Modbus

Modbus Point Mapping

The PowerSmart+ Advanced PQM provides 120 user assignable registers in the address
range of 0 to 119. You can re-map any register available in the meter to any assignable
register so that Modbus registers that reside at different locations may be simply accessed
using a single request by re-mapping them to adjacent addresses.