The following table describes available DNP options. Refer to the DNP3 Data Object
Library document available from the DNP User’s Group on the DNP3 object types.

Parameter

Options

Default

Description

Binary Inputs (BI)

Number of BI to
Generate events

0-64

3

0

The total number of BI change event
points for monitoring

Binary Input
Object

Single-bit
With Status

Single-bit

The default BI object variation for
requests with qualifier code 06 when no
specific variation is requested

Binary Input
Change Event
Object

Without Time
With Time

With Time

The default BI change event object
variation for requests with qualifier code
06 when no specific variation is
requested

Analog Inputs (AI)

Number of AI to
Generate events

0-64

3

32

The total number of AI change event
points for monitoring

Analog Input
Object

32-bit
32-bit –Flag
16-bit
16-bit –Flag

16-bit -Flag

The default AI object variation for
requests with qualifier code 06 when no
specific variation is requested

Analog Input
Change Event
Object

32-bit -Time
32-bit +Time
16-bit -Time
16-bit +Time

16-bit +Time The default AI change event object

variation for requests with qualifier code
06 when no specific variation is
requested

Binary Counters (BC)

Number of BC
to Generate
events

0-64

3

0

The total number of BC change event
points for monitoring

Binary Counter
Object

32-bit +Flag
32-bit –Flag
16-bit +Flag
16-bit –Flag

32-bit -Flag

The default BC object variation for
requests with qualifier code 06 when no
specific variation is requested

Binary Counter
Change Event
Object

32-bit -Time
32-bit +Time
16-bit -Time
16-bit +Time

32-bit +Time The default BC change event object

variation for requests with qualifier code
06 when no specific variation is
requested

Frozen Binary
Counter Object

32-bit +Flag
32-bit –Flag
32-bit +Time
16-bit +Flag
16-bit –Flag
16-bit +Time

32-bit -Flag

The default frozen BC object variation
for requests with qualifier code 06 when
no specific variation is requested