PowerSmart+ Advanced Power Quality Meter

Option

Range

Description

Num. of Records

0-65535

Allocates the file memory for predefined number of records

Record size

The size of the file record for a single channel or a section. Set
automatically depending on the file and on the number of
parameters in the data record

Parameters

0-16

The number of parameters in a single data record (not including
the EN50160 statistics files)

Memory is allocated for each file statically when you set up your files and will not change
unless you re-organize the files. The meter automatically performs de-fragmentation of the
memory each time you re-organize your files. This helps keep all free memory in one
continuous block and thus prevents possible leakage of memory caused by fragmentation.

To change the file properties or to allocate the memory for a new file, double click on the
file partition you want to change, select desired parameters for your log, and click OK. For
your reference, the record size and the number of records available for your file are
reported in the dialog box.

To delete an existing file partition, click on Delete and then click OK.

The following table shows how to calculate a file size for different log files.

File

Record Size, Bytes

File Size, Bytes

Event
Log

20

Record size × Number of records

Data Log

12 + 4 × Number of parameters

Record size × Number of records

EN50160 Compliance
Statistics, Data log #9

148 (per channel) × 12

Record size × Number of records

EN50160 Harmonics
Survey, Data log #10

220 (per channel) × 3

Record size × Number of records

TOU Profile Log, Data
log #16

12 + 4 × (Number of season
tariffs + 1 if the TOU summary
register is ordered)

Record size × Number of TOU registers x
Number of records (× 2 if the maximum
demand profile is also ordered)

Waveform Log

1068 (per channel)

Record size × Number of Channels x
Number of series (events) × Number of
records per series

EN50160 Power Quality
Log

32

Record size × Number of records

For more information on configuring specific files, see “Configuring Data Log Files” and
“Configuring Waveform Files” below.

The memory is pre-configured for common data trending and fault recording applications
as shown in the following table.

No.

File

Type

Size,

Bytes

Channels Number of

Records

Number of

Events

Description

1

Event log

Wrap
around

20000

1000

1000

2

Data log #1

Wrap
around

109440

1440

1440

Configured for data
trending

3

Data log #2

Wrap
around

109440

1440

1440

Configured for data
trending

10

Data log #9

Wrap
around

21312

12

12

12

Configured for
EN50160
compliance statistics

11

Data log #10

Wrap
around

7920

3

12

12

Configured for
EN50160 harmonics
survey

18

Waveform log #1 Wrap

around

256320 6

40

20

32 samples/cycle

x 32 cycles/series

19

Waveform log #2 Wrap

around

256320 6

40

20

128 samples/cycle
x 8 cycles/series

EN50160 Power
Quality log

Wrap
around

32000

1000

1000