E-Mon E-PS-A-RTU-N User Manual

Page 145

Advertising
background image

Appendix E EN50160 Statistics

L O G

F I L E S

PowerSmart+ Advanced Power Quality Meter

145

Appendix E EN50160 Statistics Log Files

The following table lists the EN50160 evaluation parameters recorded by the meter in the
EN50160 statistics data log files. The second column shows data abbreviations used in the
Power Software data log reports. Data log files’ sections are highlighted by a bold font.

EN50160 Compliance Statistics Log (Data Log #9)

Field No.

Designation

Description

Power Frequency

1

Nnv

Number of non-valid 10-sec intervals

2

N

Number of valid 10-sec intervals

3

N1

Number of incidents ±1%, N1

4

N2

Number of incidents +4%/-6%, N2

5

N1/N, %

EN50160 compliance ratio, N1/N

6

N2/N, %

EN50160 compliance ratio, N2/N

7

Freq Min

Minimum frequency

8

Freq Max

Maximum frequency

Supply Voltage Variations

1

Nnv

Number of non-valid 10-min intervals

2

N

Number of valid 10-min intervals

3

N1

Number of polyphase incidents ±10%, N1

4

N2

Number of polyphase incidents +10/-15%, N2

5

N1/N, %

EN50160 compliance ratio, N1/N

6

N2/N, %

EN50160 compliance ratio, N2/N

7

V1 N1

Number of incidents ±10% on phase V1

8

V1 Min

Minimum voltage on phase V1

9

V1 Max

Maximum voltage on phase V1

10

V2 N1

Number of incidents ±10% on phase V2

11

V2 Min

Minimum voltage on phase V2

12

V2 Max

Maximum voltage on phase V2

13

V3 N1

Number of incidents ±10% on phase V3

14

V3 Min

Minimum voltage on phase V3

15

V3 Max

Maximum voltage on phase V3

Rapid Voltage Changes

1

N1

Number of polyphase incidents

2

V1 N1

Number of incidents on phase V1

3

V1 dV%

Maximum voltage variation on phase V1, dV/Un%

4

V2 N1

Number of incidents on phase V2

5

V2 dV%

Maximum voltage variation on phase V2, dV/Un%

6

V3 N1

Number of incidents on phase V3

7

V3 dV%

Maximum voltage variation on phase V3, dV/Un%

Flicker

1

Nnv

Number of non-valid 10-min intervals

2

N

Number of valid 10-min intervals

3

N1

Number of polyphase incidents Plt >1%, N1

4

N1/N, %

EN50160 compliance ratio, N1/N

5

V1 N1

Number of incidents Plt > 1% on phase V1

6

V1 Plt Max

Maximum Plt on phase V2

7

V2 N1

Number of incidents Plt > 1% on phase V2

8

V2 Plt Max

Maximum Plt on phase V2

9

V3 N1

Number of incidents Plt > 1% on phase V3

10

V3 Plt Max

Maximum Plt on phase V3

Voltage Dips (indicative statistics)

1

N11 90%/100ms Number of polyphase incidents u<90%/t<100ms

2

N12 85%/100ms Number of polyphase incidents u<85%/t<100ms

3

N13 70%/100ms Number of polyphase incidents u<70%/t<100ms

4

N14 40%/100ms Number of polyphase incidents u<40%/t<100ms

5

N11 90%/500ms Number of polyphase incidents u<90%/t<500ms

6

N12 85%/500ms Number of polyphase incidents u<85%/t<500ms

7

N13 70%/500ms Number of polyphase incidents u<70%/t<500ms

8

N14 40%/500ms Number of polyphase incidents u<40%/t<500ms

9

N11 90%/1s

Number of polyphase incidents u<90%/t<1s

10

N12 85%/1s

Number of polyphase incidents u<85%/t<1s

11

N13 70%/1s

Number of polyphase incidents u<70%/t<1s

Advertising
This manual is related to the following products: