E-Mon E-PS-A-RTU-N User Manual

Page 146

Advertising
background image

Appendix E EN50160 Statistics

L O G

F I L E S

146

PowerSmart+ Advanced Power Quality Meter

Field No.

Designation

Description

12

N14 40%/1s

Number of polyphase incidents u<40%/t<1s

13

N11 90%/3s

Number of polyphase incidents u<90%/t<3s

14

N12 85%/3s

Number of polyphase incidents u<85%/t<3s

15

N13 70%/3s

Number of polyphase incidents u<70%/t<3s

16

N14 40%/3s

Number of polyphase incidents u<40%/t<3s

17

N11 90%/20s

Number of polyphase incidents u<90%/t<20s

18

N12 85%/20s

Number of polyphase incidents u<85%/t<20s

19

N13 70%/20s

Number of polyphase incidents u<70%/t<20s

20

N14 40%/20s

Number of polyphase incidents u<40%/t<20s

21

N11 90%/60s

Number of polyphase incidents u<90%/t<60s

22

N12 85%/60s

Number of polyphase incidents u<85%/t<60s

23

N13 70%/60s

Number of polyphase incidents u<70%/t<60s

24

N14 40%/60s

Number of polyphase incidents u<40%/t<60s

25

N11 90%/180s

Number of polyphase incidents u<90%/t<180s

26

N12 85%/180s

Number of polyphase incidents u<85%/t<180s

27

N13 70%/180s

Number of polyphase incidents u<70%/t<180s

28

N14 40%/180s

Number of polyphase incidents u<40%/t<180s

29

V1 N1

Total number of incidents on phase V1

30

V1 Min

Minimum residual voltage on phase V1

31

V2 N1

Total number of incidents on phase V2

32

V2 Min

Minimum residual voltage on phase V2

33

V3 N1

Total number of incidents on phase V3

34

V3 Min

Minimum residual voltage on phase V3

Voltage Interruptions (indicative statistics)

1

N1 1s

Number of polyphase incidents t<1s

2

N2 180s

Number of polyphase incidents t<180s

3

N3 >180s

Number of polyphase incidents t>180s

4

V1 Min

Minimum residual voltage on phase V1

5

V2 Min

Minimum residual voltage on phase V2

6

V3 Min

Minimum residual voltage on phase V3

Temporary Overvoltages (indicative statistics)

1

N11 110%/1s

Number of polyphase incidents u>110%/t<1s

2

N12 120%/1s

Number of polyphase incidents u>120%/t<1s

3

N13 140%/1s

Number of polyphase incidents u>140%/t<1s

4

N14 160%/1s

Number of polyphase incidents u>160%/t<1s

5

N15 200%/1s

Number of polyphase incidents u>200%/t<1s

6

N21 110%/60s

Number of polyphase incidents u>110%/t<60s

7

N22 120%/60s

Number of polyphase incidents u>120%/t<60s

8

N23 140%/60s

Number of polyphase incidents u>140%/t<60s

9

N24 160%/60s

Number of polyphase incidents u>160%/t<60s

10

N25 200%/60s

Number of polyphase incidents u>200%/t<60s

11

N31 110%/>60s Number of polyphase incidents u>110%/t>60s

12

N32 120%/>60s Number of polyphase incidents u>120%/t>60s

13

N33 140%/>60s Number of polyphase incidents u>140%/t>60s

14

N34 160%/>60s Number of polyphase incidents u>160%/t>60s

15

N35 200%/>60s Number of polyphase incidents u>200%/t>60s

16

V1 N1

Total number of incidents on phase V1

17

V1 Max

Maximum voltage magnitude on phase V1

18

V2 N1

Total number of incidents on phase V2

19

V2 Max

Maximum voltage magnitude on phase V2

20

V3 N1

Total number of incidents on phase V3

21

V3 Max

Maximum voltage magnitude on phase V3

Transient Overvoltages (indicative statistics)

1

N1 110%

Number of polyphase incidents u>120%

2

N2 150%

Number of polyphase incidents u>150%

3

N3 200%

Number of polyphase incidents u>200%

4

N4 250%

Number of polyphase incidents u>250%

5

N5 300%

Number of polyphase incidents u>300%

6

V1 N1 110%

Number of incidents u>120% on phase V1

7

V1 N2 150%

Number of incidents u>150% on phase V1

8

V1 N3 200%

Number of incidents u>200% on phase V1

9

V1 N4 250%

Number of incidents u>250% on phase V1

10

V1 N5 300%

Number of incidents u>300% on phase V1

11

V2 N1 110%

Number of incidents u>120% on phase V2

12

V2 N2 150%

Number of incidents u>150% on phase V2

Advertising
This manual is related to the following products: