PowerSmart+ Advanced Power Quality Meter

EN50160 Evaluation and Recording

EN50160 Background

EN50160 Background

EN50160 Background

EN50160 Background

The EN50160 European standard “Voltage characteristics of electricity supplied by public
distribution systems” issued by CENELEC defines the main physical characteristics of
electric energy supplied by low and medium voltage public distribution systems under
normal operating conditions.

The voltage characteristics are evaluated using a statistical approach. The standard and its
referenced publications specify for each voltage characteristic:

Method of evaluation

Integrating interval for a single measurement

Observation period

Statistical indication of the probability of not exceeding a specified limit

Standard compliance limits or indicative values within which any customer can expect the
voltage characteristics to remain

Compliance Limits

For some voltage characteristics, the standard provides definite limits that can be complied
with for most of the time considering the possibility of relatively rare excursions beyond
these limits. Limits are set with a view to compliance for a percentage of the observation
time, e.g. 95% of the observations in any period of one week.

The following table gives the characteristics for which definite limits have been specified by
the standard.

Indicatives Values

For the remaining characteristics of the voltage, by their unpredictable nature, the standard
gives only indicative values, which are intended to provide users with information on the
order of magnitude which can be expected.

The following table gives the characteristics for which indicative values have been specified
by the standard.

Voltage
Characteristic

Indicative

values

Observation

period

Voltage dips

Less than 1 s, 60% depth

Year

Short interruptions

70% less than 1 s

Year

Long interruptions

10 to 50% less than 3 min Year

Temporary overvoltages

Less than 1.5 kV RMS

Year

Transient overvoltages

Less than 6 kV peak

Year

Voltage characteristic

Compliance with stated

limits, % of time

Observation

period

Power frequency

±

1% for 95% of a week

±

1% for 99.5% of a year

+4/-6% for 100% of time

Week, year

Voltage variations (supply
voltage magnitude)

±

10% Un for 95% of time

Week

Rapid voltage changes

4-5% Un (up to 10% Un)

Day

Flicker (fluctuations of
voltage magnitude)

Plt ≤ 1 for 95% of time

Week

Voltage unbalance

2-3% for 95% of time

Week

Harmonic voltage

THD ≤ 8 for 95% of time

Week

Interharmonic voltage

To be defined

Week

Mains signaling voltage

Within “Meister-curve” for
99% of time

Day