Appendix f data scales – E-Mon E-PS-A-RTU-N User Manual

Page 149

Advertising
background image

Appendix F Data Scales

PowerSmart+ Advanced Power Quality Meter

149

Appendix F Data Scales

The maximum values for volts, amps and power in the PowerSmart+ Advanced PQM setup
and in communications are limited by the voltage and current scale settings. See

Device

Options

in Chapter 4 on how to change the voltage scale in your meter.

The following table defines the meter data scales.

Scale

Conditions

Range

Maximum voltage
(V max)

All configurations

Voltage scale × PT Ratio, V

1

Maximum current
(I max)

All configurations

Current scale × CT Ratio, A

2, 3

Wiring 4LN3, 3LN3, 3BLN3

V max × I max × 3, W

Maximum Power
(P max)

4

Wiring 4LL3, 3LL3, 3BLL3,
3OP2, 3OP3, 3DIR2

V max × I max × 2, W

Maximum
frequency

50 or 60 Hz

100 Hz

1

The default voltage scale is 144V. The recommended voltage scale is 120V+20% = 144V

for using with external PT’s, and 690V+20% = 828V for a direct connection to power line.

2

CT Ratio = CT primary current/CT secondary current

3

The default current scale is 2

×

CT secondary (2.0A with 1A secondaries and 10.0A with 5A

secondaries)

.

4

Maximum power is rounded to whole kilowatts. With PT=1.0, it is limited to 9,999,000 W.

Advertising