Timers setup, Display setup – E-Mon E-PS-A-RTU-N User Manual

Page 51

Advertising
background image

Chapter 3 Display

O P E R A T I O N S

M E N U O P E R A T I O N S

PowerSmart+ Advanced Power Quality Meter

51

Analog expander outputs are not operational until you globally enable the analog expander option

in your meter through the

Device Options

menu.

Timers Setup

Timers Setup

Timers Setup

Timers Setup

The PowerSmart+ Advanced PQM is provided with four interval timers. When
enabled, a timer generates periodic events in predefined intervals that can trigger
setpoints to produce periodic actions like periodic data trending. To enter the menu,
select the “t-r” entry from the main menu and press the ENTER button.

Use the UP and DOWN arrow buttons to scroll to the desired timer.

To change the time period for the timer:

Press the SELECT button to activate the lower window.

Use the UP and DOWN arrow buttons to enter the desired interval value in seconds.
Intervals from 1 to 9999 seconds are allowed. Resetting the interval to 0 disables
the timer.

Press ENTER to confirm your changes and to save the new settings, or press ESC
to discard changes.

You are returned to the middle window to select another timer or exit the menu.

To exit the menu, press ESC.

Display Setup

Display Setup

Display Setup

Display Setup

This menu allows you to configure options for the meter display, and view display
and device firmware versions. To enter the menu, select the “diSP” entry from the
main menu and press the ENTER button.

To select a setup option:

Press the SELECT button to activate the middle window.

Use the UP and DOWN arrow buttons to scroll to the desired option.

To change the option:

Press the SELECT button to activate the lower window.

Use the UP and DOWN arrow buttons to select the desired option.

Press ENTER to confirm the changes and to save your new setting, or press ESC to
discard changes.

To exit the menu, press ESC.

The following table lists available options.

Label

Parameter

Options

Default

Description

UPdt

Display update rate 0.1-10.0 sec 1 sec

Defines the interval between
display updates

ScrL

Auto scroll interval

None,

2-15 sec

None

Defines the scroll interval for
the main data display or
disables auto scroll

rEtn

Auto return to the
main screen

diS =
disabled,
En =
Enabled

Enabled

Enables automatic return to
the main display if no buttons
are pressed for 5 minutes

bAr

Reference load
current for LED bar
graph

0-20,000A
(0 = CT
primary
current)

0

Defines the nominal load
(100%) level for the bar
graph display

t-r

0

t-r.1

diSP

1.0