Appendix A Technical Specifications

130

PowerSmart+ Advanced Power Quality Meter

Measurement Specifications

Accuracy

Parameter

Full Scale @ Input

Range

%

Reading

% FS

Conditions

Range

Voltage

120VxPT @ 120V

400VxPT @ 690V

0.2

0.01

10% to 120% FS

0 to 1,150,000 V

Starting voltage

1.5% FS @ 120V

1.5% FS @ 690V

Line current

CT

0.2

0.02

1% - 200% FS

0 to 40,000 A

Starting current 0.1% FS

Active power

0.36×PT×CT @ 120V

1.2×PT×CT @ 690V

0.2

0.02

|PF| ≥ 0.5

1

-10,000,000 kW to

+10,000,000 kW

Reactive power

0.36×PT×CT @ 120V

1.2×PT×CT @ 690V

0.3

0.04

|PF| ≤ 0.9

1

-10,000,000 kvar to

+10,000,000 kvar

Apparent power

0.36×PT×CT @ 120V

1.2×PT×CT @ 690V

0.2

0.02

|PF| ≥ 0.5

1

0 to 10,000,000 kVA

Power factor

1.000

0.2

|PF| ≥ 0.5,

I ≥ 2% FSI

-0.999 to +1.000

Frequency

0.02

40 Hz to 70 Hz

Total Harmonic
Distortion, THD
V (I), %Vf (%If)

999.9

1.5

0.1

THD ≥ 1%,

V (I) ≥ 10% FSV
(FSI)

0 to 999.9

Total Demand
Distortion, TDD,
%

100

1.5

TDD ≥ 1%,

I ≥ 10% FSI

0 to 100

Active energy
Import & Export

Class 0.2S under conditions as per IEC
62053-22:2003

0 to 999,999.999 MWh

Reactive energy
Import & Export

Class 0.2S under conditions as per IEC
62053-22:2003, |PF| ≤ 0.9

0 to 999,999.999 Mvarh

Apparent energy

Class 0.2S under conditions as per IEC
62053-22:2003

0 to 999,999.999 MVAh

1

@ 80% to 120% of voltage FS, 1% to 200% of current FS, and frequency 50/60 Hz

PT - external potential transformer ratio

CT - primary current rating of external current transformer

FSV - voltage full scale

FSI - current full scale

Vf - fundamental voltage

If - fundamental current

NOTES

1. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit.
This does not include inaccuracies introduced by the user's potential and current
transformers. Accuracy calculated at 1second average.

2. Voltage and Current measurement accuracy is ≤ 0.05 % at nominal value

3. Specifications assume: voltage and current waveforms with THD ≤ 5% for kvar, kVA
and PF, and reference operating temperature 20°C - 26°C.

4. Measurement error is typically less than the maximum error indicated.