E-Mon E-PS-A-RTU-N User Manual

Page 7

Advertising
background image

Chapter 1 General Information

Mechanical Installation

PowerSmart+ Advanced Power Quality Meter

7

16 data recorders; programmable data logs on a periodic basis

and on any internal and external trigger

Two waveform recorders; simultaneous 6-channel AC recording

in a single plot; sampling rate of 32, 64 and 128 samples per
cycle; 20 pre-fault cycles; up to 30 seconds of continuous
recording at a rate of 32 samples per cycle

EN50160 Power Quality recorder (EN50160 compliance

statistics, EN50160 harmonics survey statistics, onboard power
quality analyzer; programmable thresholds and hysteresis;
ready-for-use reports)

Real-time waveform capture and monitoring; simultaneous 6-

channel 4-cycle capture at 128 samples per cycle

Easy to read 3-row (2x4 characters + 1x6 characters) bright LED

display, adjustable update time, auto-scroll option with adjustable
page exposition time, auto-return to a default page

LED bar graph showing percent load with respect to user-

definable nominal load current

Detachable display module with a 3-wire RS-485 interface; up to

1000 meters operation

2 digital inputs for monitoring external contacts, and receiving

pulses from energy, water and gas meters

2 relay outputs for alarms and controls, and for output energy

pulses

2 optional optically isolated analog outputs with an internal

power supply; options for 0-20mA, 4-20mA, 0-1mA, and ± 1mA
output

2 optional optically isolated analog inputs with an internal power

supply; options for 0-20mA, 4-20mA, 0-1mA, and ± 1mA input

Optional analog expander providing additional 2 x 8 analog outputs; options for
0-20mA, 4-20mA, 0-1mA, and ± 1mA 50/60 Hz operation

Precise internal clock with battery backup

1 Mbyte RAM with battery backup for long-term data and waveform recording

Two communication ports; communications options available:

COM1:

RS-232/RS-422/RS-485

56K Dial-up modem

Ethernet 10/100BaseT, eXpertPower enabled

COM2:

RS-422/RS-485

Modbus RTU, Modbus ASCII and Modbus/TCP, DNP3 and DNP3/TCP (with
firmware V25.2.01 and later) communication protocols

Password security for setup parameters and resets via the front panel and
communications. Recording of tampering attempts to the device event log.

Easy field upgrading device firmware through any communication port

Advertising