Chapter 3 Display

O P E R A T I O N S

M E N U O P E R A T I O N S

46

PowerSmart+ Advanced Power Quality Meter

COM2 Settings

Label

Parameter

Options

Default

Description

Prot

Communications
protocol

rtu = Modbus RTU
ASCII = Modbus
ASCII

dnP3 = DNP3

Modbus
RTU

The communications
protocol supported by
the port

rS

Port interface

485 = RS-485
422 = RS-422

RS-485

Addr

Device address

Modbus: 1-247
DNP3: 0–65532

1

Device network address

bAud

Baud rate

300-115200 bps

19200 bps The port baud rate

dAtA

Data format and
parity

7E, 8N, 8E

8N

7E data format should
not be used with the
Modbus RTU and DNP3
protocols

Network Address

Network Address

Network Address

Network Address

This menu allows you to configure the device IP address and the default gateway
address for the Ethernet port. To enter the menu, select “nEt” from the main menu,
and then press the ENTER button.

To change the IP Address and Default Gateway:

To change the device IP address, select the “A” entry in the upper window with the UP and
DOWN arrow buttons. To change the default gateway address, select the “G” entry.

Press the SELECT button to activate the first address digit.

Use the UP and DOWN arrow buttons to adjust the digit.

Press the SELECT button to advance to the next digit.

Adjust the remaining address digits.

Press ENTER to confirm your new setting, or press ESC to discard changes.

To exit the menu, press ESC.

Counters Setup

Counters Setup

Counters Setup

Counters Setup

The PowerSmart+ Advanced PQM has four six-digit counters that can count pulses
delivered through the device digital inputs with a programmable scale factor, or events that
trigger setpoint operations. This menu allows you to link digital inputs to the counters and
define a pulse multiplier for each counter. To enter the menu, select the “Cnt” entry from
the main menu and press the ENTER button.

The menu uses three entries:

The upper window indicates a counter number.

The middle window selects a digital input to be linked to the counter.

The lower window defines a counter multiplier.

Use the UP and DOWN arrow buttons to scroll to the desired counter.

To change the counter options:

Press the SELECT button to activate the middle window.

Use the UP and DOWN arrow buttons to link a digital input to the counter or to disable the
counter input.

Press the SELECT button to activate the lower window.

Cnt.1

1

Inp.1

A

.

000.203

G

.

000.001