E-Mon E-PS-A-RTU-N User Manual

Page 54

Advertising
background image

Chapter 3 Display

O P E R A T I O N S

M E N U O P E R A T I O N S

54

PowerSmart+ Advanced Power Quality Meter

The Reset menu allows you to separately reset minimum/maximum log records,
maximum demands and counters.

To reset the desired registers:

Highlight the middle window by pressing briefly the SELECT button.

Select the desired entry by scrolling through the list with the UP and DOWN arrow
buttons until the desired entry appears.

Press the SELECT button briefly to highlight the lower item.

Press and hold the ENTER button for 5 seconds.

Release the button. The “do” entry is replaced with “done” showing the operation is
complete.

The following table shows available options.

Label

Description

Lo.Hi

Clears Min/Max log

A.dnd

Clears maximum ampere, volt and harmonic demands

P.dnd

Clears maximum power demands

dnd

Clears all maximum demands

Enr

Clears all total energies

tOU.d

Clears summary and TOU maximum demands

tOU.E

Clears summary and TOU energy registers

Cnt

Clears all counters

Cnt1 – Cnt4 Clears counter #1-#4