E-Mon E-PS-A-RTU-N User Manual

Page 44

Advertising
background image

Chapter 3 Display

O P E R A T I O N S

M E N U O P E R A T I O N S

44

PowerSmart+ Advanced Power Quality Meter

Label Parameter

Options

Default

Description

P.cAL Power

calculation
mode

rEAc (reactive power),
nAct (non-active
power)

Reactive

The method used for
calculating reactive and
apparent powers

roLL

Energy roll
value

E

10.E4=10,000
10.E5=100,000
10.E6=1,000,000

10.E7=10,000,000

10.E8=100,000,000
10.E9=1,000,000,000

10.E9

The value at which
energy counters roll
over to zero

Ph.En Phase energy

option

E

diS = disabled
En = enabled

Disabled

Enables phase energy
calculations

bAtt

Backup battery
mode

OFF = switched OFF
On = switched ON

OFF

Allows to conserve a
battery while the meter
is out of operation

tESt

Energy test
mode

OFF = disabled
Ac.Ei = Wh pulses
rE.Ei = varh pulses

Disabled

Setting this option puts
the meter into the
energy test mode

An.EP Analog

expander
option

1

nonE = disabled

0-20 = 0-20 mA

4-20 = 4-20 mA
0-1 = 0-1 mA
-1-1 = ±1 mA

Disabled

Enables outputs for the
AX-8 analog expanders
through port COM2. See
“Analog Expander
Setup”

1

Do not enable the analog expander output if you do not have the analog expander

connected to the meter, otherwise it will disturb the computer communications.