B.4 template 4: dual hazard - split release, B.4: template 4: dual hazard - split release – System Sensor PDRP-2001 User Manual

Page 116

Advertising
background image

116

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

FACP Configuration Templates

Template 4: Dual Hazard - Split Release

B.4 Template 4: Dual Hazard - Split Release

Table Legend:

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).

Input Zone Types:

Zone 1 = 2-wire smoke

Zone 2 = Fire

Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay Timer 10 set to
secs.)

Zone 4 = Supervisory

Zone 5 = Manual Release

Zone 6 = Pull Station

Output Circuit Types:

Output 1 = Alarm NAC, silenceable, coded for steady on

Output 2 = Supervisory Bell NAC, silenceable, coded for steady on

Output 3 = Release Solenoid 1 (unsupervised for shorts)

Output 4 = Release Solenoid 2 (unsupervised for shorts)

Timers

Soak Timer 1 - set for 10 minutes

Soak Timer 2 - set for 10 minutes

Waterflow Delay Timer - set for 10 seconds

AC Loss Delay Timer - set for 2 hours

Operation

Activation of Input Zone 1 (2-Wire Smoke) will operate Release Solenoid 1 Output #3 and
Alarm NAC Output #1. Activation of Input Zone 2 (Fire) will operate Release Solenoid 2 Out-
put #4 and Alarm NAC Output #1. Activation of Input 5 (Manual Release) or Input 6 (Manual
Pull Station) will operate Solenoid 1 Output #3 and Solenoid 2 (Output #4) and Alarm NAC
Output #1. Release Solenoid 1 will turn off water release following time-out of the 10 minute
Soak Timer 1 and Release Solenoid 2 will turn off water release following time-out of the 10
minute Soak Timer 2

Activation of Input Zone 3 (Waterflow) will operate the Alarm NAC Output #1. There is a 10
second FACP initiated delay in activation since Waterflow Delay Timer is set to 10 seconds

Activation of Input Zone 4 (Supervisory) will operate the Supervisory Bell NAC Output #2

Template 4: DUAL HAZARD - SPLIT RELEASE

INPUT ZONES

1

2

3

4

5

6

OUTPUT CIRCUITS

2-WIRE SMOKE

FIRE

WATERFLOW

SUPV.

MANUAL

RELEASE

PULL

STATION

#1 ALARM NAC

X

X

X

X

X

#2 SUPV BELL NAC

X

#3 RELEASE SOLENOID 1

X

X

X

#4 RELEASE SOLENOID 2

X

X

X