NFPA 72 Auxiliary Fire Alarm System

NFPA Standard-Specific Requirements

C.1 NFPA 72 Auxiliary Fire Alarm System

All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.

Notes:

1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2. Cut JP30 on the PDRP-2001 main circuit board to supervise placement of 4XTMF module and

circuit.

3. Cut JP24 on the PDRP-2001 main circuit board to enable FACP Supervisory relay.
4. Refer to “4XTMF Municipal Box Transmitter Option Module” on page 31 for detailed

information.

FIRE

Gamewell Model M34-56 Local

Energy Municipal Box

Polarities shown in alarm condition

+

Nonpower-limited

Municipal Box Circuit

+

-

-

4XTMF

Figure C.2 Municipal Box Connected to 4XTMF Transmitter Module