B.7 template 7: single hazard - dual zone, B.7: template 7: single hazard - dual zone – System Sensor PDRP-2001 User Manual

Page 122

Advertising
background image

122

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

FACP Configuration Templates

Template 7: Single Hazard - Dual Zone

B.7 Template 7: Single Hazard - Dual Zone

Table Legend:

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).

Input Zone Types:

Zone 1 = 2-wire smoke

Zone 2 = Fire

Zone 3 = Low Pressure

Zone 4 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)

Zone 5 = Pull Station

Zone 6 = Manual Release

Output Circuit Types:

Output 1 = Alarm NAC, silenceable, coded for steady on

Output 2 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10
secs.), silenceable, coded for steady on

Output 3 = Release Solenoid 1 (unsupervised for shorts)

Output 4 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10
secs.), silenceable, coded for steady on

Timers

Soak Timer 1 - set for 10 minutes

Soak Timer 2 - set for 10 minutes

Waterflow Delay Timer - set for 10 seconds

AC Loss Delay Timer - set for 2 hours

Operation

Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 5 (Pull Station) or Zone
6 (Manual Release) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output #3.
Release Solenoid will turn off water release following time-out of the 10 minute Soak Timer 1

Activation of Input Zone 4 (Waterflow) will operate the Alarm NAC Output #1, Waterflow
NAC Output #2 and Waterflow NAC Output #4. There is a 10 second FACP initiated delay in
activation of these outputs since the Waterflow Delay Timer is set to 10 seconds

Activation of Input Zone 3 (Low Pressure) will not operate any Output Circuits (see Relays)

Template 7: SINGLE HAZARD - DUAL ZONE

INPUT ZONES

1

2

3

4

5

6

OUTPUT CIRCUITS

2-WIRE SMOKE

FIRE

LOW

PRESS.

WATERFLOW

PULL

STATION

MANUAL

RELEASE

#1 ALARM NAC

X

X

X

X

X

#2 WATERFLOW NAC

X

#3 RELEASE SOLENOID 1

X

X

X

X

#4 WATERFLOW NAC

X