2.7.1 ANN-BUS Wiring

This section contains information on calculating ANN-BUS wire distances and the types of wiring
configurations (Class B).

Calculating Wiring Distance for ANN-BUS Modules

The following instructions will guide the installer in determining the type of wire and the maximum
wiring distance that can be used with FACP ANN-BUS accessory modules.

To calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is
necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus.
The total worst case current draw is calculated by adding the individual worst case currents for each
module. The individual worst case values are shown in the following table:

After calculating the total worst case current draw, Table 2.1 specifies the maximum distance the
modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of line
drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges,
capacitance is the limiting factor.

These cases are marked in the chart with an asterisk (*). Maximum length can never be more than
6,000 feet (1,800 m), regardless of gauge used. The formula used to generate this chart is shown in
the note below.

Model Number

Worst Case Current Draw

1

1 Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp.

ANN-80(C) LCD Annunciator/Indicator

0.040 amps

ANN-S/PG Serial/Parallel Printer Interface Module

0.040 amps

ANN-I/O LED Driver Module

0.200 amps

ANN-LED Annunciator Module

0.068 amps

ANN-RLY Relay Module

0.075 amps

Wiring Distance: ANN-BUS Modules to FACP

1

Total Worst Case Current

Draw (amps)

22 Gauge

18 Gauge

16 Gauge

14 Gauge

0.100

1,852 ft.

4,688 ft.

* 6,000 ft.

*6,000 ft.

0.200

926 ft.

2,344 ft.

3,731 ft.

5,906 ft.

0.300

617 ft.

1,563 ft.

2,488 ft.

3,937 ft.

0.400

463 ft.

1,172 ft.

1,866 ft.

2,953 ft.

0.500

370 ft.

938 ft.

1,493 ft.

2,362 ft.

Table 2.1 Wiring Distances

1

The following formulas were used to generate the wire distance chart:

Maximum Resistance (Ohms)

=

6.0 Volts

Total Worst Case Current Draw (amps)

Maximum Wire Length (feet)

(6,000 feet maximum)

=

Maximum Resistance (Ohms)

*500

Rpu

where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)