System Sensor PDRP-2001 User Manual

Page 14

Advertising
background image

14

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

Product Description

Specifications

Battery (sealed lead acid only) - J12

Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp
Supervised, nonpower-limited
Maximum Charger Capacity: 26 Amp Hour battery (two 18 Amp Hour batteries can be housed in
the FACP cabinet.Larger batteries require a separate battery box such as the BB-26 or BB-55F and
the CHG-75 or CHG-120F Battery Charger.)
Minimum Battery Size: 7 Amp Hour
Canadian Applications
Minimum Battery Size: 12 Amp Hour
Maximum Battery Size: 18 Amp Hour

Initiating Device Circuits - TB4 and TB6

Alarm Zones 1 - 5 on TB 4
Alarm Zone 6 on TB6
Supervised and power-limited circuitry
Operation: All zones Style B (Class B)
Normal Operating Voltage: Nominal 20 VDC
Alarm Current: 15 mA minimum
Short Circuit Current: 40 mA max.
Maximum Loop Resistance: 100 ohms (700 ohms for linear heat detection - See Section 2.3, “Input
Circuits” fo
r more information.)
End-of-Line Resistor: 4.7K

, 1/2 watt (Part #71252)

Standby Current: 2 mA
Refer to the Device Compatibility Appendix for listed compatible devices

Notification Appliance and Releasing Circuit(s) - TB5 and TB7

Four Output Circuits
Operation: Style Y (Class B)
Special Application power
Supervised and power-limited circuitry
Normal Operating Voltage: Nominal 24 VDC
Maximum Signaling Current: 7.0 amps (3.0 amps maximum per NAC)
End-of-Line Resistor: 4.7K

, 1/2 watt (Part #71252)

Refer to “Wire Requirements” on page 134 for wire specifications
Refer to the Device Compatibility Appendix for compatible listed devices

Form-C Relays - Programmable - TB8

Relay 1 (factory default programmed as Alarm Relay)
Relay 2 (factory default programmed as fail-safe Trouble Relay)
Relay 3 (factory default programmed as Supervisory Relay)
Relay Contact Ratings: 2 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive)

Auxiliary Trouble Input - J6

The Auxiliary Trouble Input is an open collector, unsupervised circuit which can be used to
monitor external devices for trouble conditions. It can be connected to the trouble bus of a
peripheral, such as a power supply, which is compatible with open collector circuits.
All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.

Special Application Resettable Power - TB9

Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors
Power-limited Circuitry
Refer to the Device Compatibility Appendix for compatible listed devices