PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

Programming

Master Programming Level

To change the programming for the displayed zone, press the keyboard ‘down’ arrow key to view
the Edit Zone screens.

The following examples show the editing of Input Zone 1:

Enable/Disable Zone

To Enable or Disable the zone, press the 1 key while viewing the Edit Input Zone Screen #2. Each
press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is
selected, the zone will be disabled by the control panel, preventing the circuit from reporting alarms
and troubles to the panel. The control panel LCD will display the zone which has been disabled
and FACP will turn on the Trouble indicator.

Type

To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone
Screen #2. This will cause the control panel to display the following Zone Type Screen:

INPUT ZONE 1
1=ENABLED YES
2=TYPE PULL STATION

Edit Input Zone Screen #2

Edit Input Zone Screen #3

INPUT ZONE 1
1=OUTPUT CIRCUIT MAP
2=FREEZE SUPV. YES

Edit Input Zone Screen #3

INPUT ZONE 1
1=ADJECTIVE/NOUN
2=DESCRIPTION
********************

INPUT ZONE

1=ENABLED
2=TYPE

Edit Input Zone Screen #2

ZONE 1 TYPE
1=PULL STATION
2=N/A
3=MANUAL RELEASE

Zone Type Screen #1