9 walktest, Walktest – System Sensor PDRP-2001 User Manual

Page 80

Advertising
background image

80

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

Programming

Master Programming Level

3.5.9 Walktest

Walktest allows an individual to test the fire alarm system without the necessity to reset the control
panel after each device activation. Pressing 3 while viewing the Programming Screen #3 will cause
the following Walktest options to be displayed:

To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest
Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the
following screen will be displayed:

The user can now perform a one-person walktest by activating devices throughout the system. As
each device is activated, the screen will display the information about the activated device as shown
below. Note that the colon (:) in the time is replaced with an asterisk (*) to distinguish the
walktest screen from an actual alarm screen.

After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to
the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing
the Walktest Screen. The following screen will be displayed:

Use the up and down arrow keys to view all of the walktest results which will be displayed as
illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC
and DC) is removed from the FACP, the Walktest log information will be lost. This information is
also overwritten when subsequent walktests are performed.

PROGRAMMING

1=ANN-BUS
2=HISTORY
3=WALKTEST

Programming Screen #3

WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW EVENTS

Walktest Screen


UNIT IN WALKTEST

Walktest Active Screen

ALARM ZONE 1
<ADJ> <NOUN>
Z01
10*00A 010805

WALKTEST EVENTS