2 specifications, Specifications – System Sensor PDRP-2001 User Manual

Page 13

Advertising
background image

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

13

Specifications

Product Description

Indicators

Fire Alarm

Supervisory

Trouble

AC Power

Alarm Silenced

Discharge

Piezo sounder for alarm, trouble and supervisory

24 volt operation

Low AC voltage sense

Outputs Programmable for:

Releasing Solenoids

NACs programmable for:

– Silence Inhibit
– Auto-Silence
– Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)
– Selective Silence (horn-strobe mute)
– Temporal or Steady Signal
– Silenceable or Nonsilenceable
– Release Stage Sounder

Designed for sprinkler standards NFPA 13, 15 and 16

Disable/Enable control per input zone and output zone

Extensive transient protection

Dual hazard operation

Adjustable waterflow discharge timer and two soak timers

Cross-zone (double-interlock) capability

Pre-programmed and custom application templates

Automatic battery charger with charger supervision

Silent or audible walktest capabilities

Optional Dress Panel DP-51050 (red)

A modified Dress Panel is provided standard with Canadian models: includes an ANN-LED
Annunciator module

Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet

Optional CAC-5X Class A Converter Module for Outputs and IDCs

Optional 4XTMF Municipal Box Transmitter Module

Optional Digital Alarm Communicators (411, 411UD, 411UDAC)

Optional ANN-SEC card for secondary ANN-BUS

1.2 Specifications

AC Power

PDRP-2001/C: 120 VAC, 60 Hz, 3.66 amps
PDRP-2001E: 240 VAC, 50 Hz, 2.085 amps
Wire size: minimum #14 AWG (2.0 mm

2

) with 600V insulation

Supervised, nonpower-limited