System Sensor PDRP-2001 User Manual

Page 118

Advertising
background image

118

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

FACP Configuration Templates

Template 5: Single Hazard - 3 Zones and Low Pressure

B.5 Template 5: Single Hazard - 3 Zones and Low Pressure

Table Legend:

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).

Input Zone Types:

Zone 1 = 2-wire smoke

Zone 2 = Fire

Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)

Zone 4 = Manual Release

Zone 5 = Pull Station

Zone 6 = Low Pressure

Output Circuit Types:

Output 1 = Alarm NAC, silenceable, coded for steady on

Output 2 = Waterflow NAC - activation delayed for 10 secs. (Waterflow Delay set to10 secs.),
silenceable, coded for steady on

Output 3 = Supervisory Bell NAC, silenceable, coded for steady on

Output 4 = Release Solenoid 1 (unsupervised for shorts)

Timers

Soak Timer 1 - set for 10 minutes

Soak Timer 2 - set for 10 minutes

Waterflow Delay Timer - set for 10 seconds

AC Loss Delay Timer - set for 2 hours

Operation

Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or
Zone 5 (Pull Station) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output
#4. Release Solenoid 1 will turn off water release following time-out of the 10 minute Soak
Timer 1

Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is a
10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10 seconds

Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3

Template 5: SINGLE HAZARD - 3 ZONES AND LOW PRESSURE

INPUT ZONES

1

2

3

4

5

6

OUTPUT CIRCUITS

2-WIRE SMOKE

FIRE

WATERFLOW

MANUAL

RELEASE

PULL

STATION

LOW

PRESS.

#1 ALARM NAC

X

X

X

X

#2 WATERFLOW NAC

X

#3 SUPV. BELL NAC

X

#4 RELEASE SOLENOID 1

X

X

X

X