Master Programming Level

Programming

Pressing the down arrow key displays additional zone types as indicated in the following table.

While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.

Zone Type

Action When Activated

Pull-Station

Fire Alarm

Manual Release

1

1 Activation of a Manual Release Switch will override Predischarge Delay, resulting

in an immediate water release.

Fire Alarm

N/A

Normally Open Contact

Fire

N/A

N/A

N/A

Waterflow

Fire

Waterflow NS (nonsilenceable)

Fire, nonsilenceable

Combo

Fire/Supervisory

Combo w/AutoResettable Superv

2

2 AutoResettable means that a device with this type code, when activated, will

automatically reset when the corresponding condition is cleared.

Fire/Supervisory, nonlatching

2-Wire Smoke

Fire Alarm

2-Wire Heat

Fire Alarm

N/A

Linear Heat

Fire Alarm

N/A

N/A

Fire

Fire Alarm

Low Pressure

Supervisory, latching

Low Pressure AutoResettable2

Supervisory, nonlatching

High Pressure

Supervisory

High Pressure AutoResettable2

Supervisory, nonlatching

Disable Release

3

3 Disable Release allows the installer to disable the releasing solenoids during

system testing. Disable Release will only work when the system is not in alarm.

Supervisory, nonlatching (disables Release Circuits)

Supervisory

Supervisory, latching

Supervisory AutoResettable2

Supervisory, nonlatching

N/A

2nd-Shot Water Switch

4

4 The 2nd-Shot Water Switch provides the option of performing another immediate

water release manually. Refer to “2nd-Shot Water Switch” on page 91.

Fire Alarm, nonlatching

Table 3.1 Zone Types