PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

NFPA Standard-Specific Requirements

NFPA 72 Auxiliary Fire Alarm System

NFPA 72 Remote Station Protective Signaling System

Notes:

1. Cut Jumper JP30 on the PDRP-2001 main circuit board to supervise placement of the 4XTMF

module.

2. Refer to “4XTMF Transmitter Module Installation” on page 31 for detailed information.

RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver Model RS82.

+ -

Polarity Shown is
Normal Standby

4XTMF Transmitter Module

Cutting TBL Jumper allows the
reverse polarity circuit to open with
a system trouble condition if no
alarm condition exists.

Power-limited

Figure C.3 Remote Station Connection Using 4XTM Module

+

-

(Dummy load with a 4.7K

¼ watt resistor

when no connection is made)