3 controls and indicators, Controls and indicators – System Sensor PDRP-2001 User Manual

Page 16

Advertising
background image

16

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

Product Description

Controls and Indicators

1.3 Controls and Indicators

LCD Display

The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED
backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED
backlight will turn off to conserve batteries.

Key Panel

Mounted on the main circuit board, the key panel includes a window for the LCD display and
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.

Function keys:

Acknowledge/Step

Alarm Silenced

Drill

System Reset (lamp test)

Service/program keys:

Keys labeled 1 to 9

* key

# key

0 (recall) key

1st Event key

Clear key

Escape key

Mode key

Four cursor keys (up, down, left and right)

Enter key

Local Piezo Sounder

A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory
conditions.

Indicators

Indicators are provided to annunciate the following conditions:

Fire Alarm - red indicator

Supervisory - yellow indicator

AC Power - green indicator

System Trouble - yellow indicator

Alarm Silenced - yellow indicator

Discharge - red indicator

Local Piezo Sounder

A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and
supervisory conditions as follows:

Alarm - on steady

Trouble - pulse 1 second on and 1 second off

Maintenance - pulse ½ second on and ½ second off

Supervisory - pulse ½ second on and ½ second off

Figure 1.2 Membrane/Display Panel

MR

P

200

1kyp

d.cd

r

Advertising