PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

25

Input Circuits

Installation

Combination Waterflow/Supervisory Zone

A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm
switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. Any
circuit can be programmed as a Combo Type zone. The following figure illustrates the wiring of
Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit.

Requirements for the Combination Waterflow/Supervisory circuit are as follows:

This circuit is only intended for one Waterflow and one Supervisory device.

The Waterflow Alarm Switch must connect to the FACP Initiating Device Circuit before the
In-Line Resistor as shown in Figure 2.6.

The Supervisory Switch must connect to the FACP Initiating Device Circuit after the In-
Line Resistor as shown in Figure 2.6.

Program the FACP Initiating Device Circuit as a Combination circuit as described in “Input
Zones” on page 51.
Note that since a Waterflow Supervisory Switch is included in a
Combination circuit, the waterflow delay must be taken into consideration. Refer to
“Waterflow Delay” on page 68.

Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm
condition is cleared and the FACP is reset

Supervisory Switch activation causes the panel to latch the supervisory condition if the
Combo type code is selected or track (the panel will clear when the supervisory condition is
cleared) if the Combo Autoresettable Supervisory type code is selected.

Class B Initiating Device Circuits (supervised and power-limited)

4.7 K

, ½ watt resistor P/N:71252

In-Line-Resistor

1.2 K

, ½ watt resistor P/N: 75579

Alarm Switch
(waterflow)

Dummy load all unused

circuits - 4.7 K

, ½ watt

resistor (P/N: 71245)

Figure 2.6 Style B Combination Circuit on Zone 2

Supervisory Switch
(tamper)