Specifications, Prn-6f printer installation, Specifications prn-6f printer installation – System Sensor PDRP-2001 User Manual

Page 40

Advertising
background image

40

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

Installation

ANN-BUS Devices

2. Connect the ANN-S/PG to the FACP as illustrated in Figure 2.19

3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address)

to the module

4. Select the address and configuration options for the ANN-S/PG module as described in the

Programming section of this manual (refer to “ANN-BUS” on page 73)
Note that the Auto-configure feature allows the programmer to quickly bring all installed
ANN-BUS modules online (refer to “Auto-Configure” on page 75)

5. Connect a printer to the ANN-S/PG Parallel or Serial connector (refer to Figure 2.19 on page

40)

Specifications

Operating Voltage: 24 VDC

Current (Alarm and Standby): 45 mA

Ambient Temperature: 32

o

F to 120

o

F (0

o

C to 49

o

C)

Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)

Mounting: Surface

Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)

For indoor use in a dry location only

PRN-6F Printer Installation

When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the status changes
within the control panel and time-stamps the printout with the time of day and date that the event
occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This section
contains information on connecting a printer to the control panel and setting the printer options.

Connecting PRN-6F Printer

Remote printers require a primary AC power source. If required for the fire alarm system
configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Since a secondary power source is not provided as a
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used. The
building emergency power supply may be used, as long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.

Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 cable.
One end of the cable will plug into the DB-25 connector on the PRN-6F printer and the other end
plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB-9 port on the
ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a Centronics parallel
printer cable. Connect either a serial or parallel printer, but not both at the same time.

Figure 2.19 ANN-S/PG Connection to FACP

ANN-S/PG Module

FACP

Cable

Connectors

for connection

to printer

Parallel

Serial

ANN-BUS and power wiring are
supervised and power-limited

TB3

ann

S

P

G

rp

20

01

.cdr

Primary ANN-BUS

Advertising