G.2 maximum number of detectors per zone, G.2: maximum number of detectors per zone – System Sensor PDRP-2001 User Manual

Page 137

Advertising
background image

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

137

Maximum Number of Detectors per Zone

Compatible Devices

G.2 Maximum Number of Detectors per Zone

When using two-wire smoke detectors containing supplementary relays or indicators, the operation
of more than one detector per zone cannot be ensured

Model Number

Base Model

Number of

Devices

2W-B

N/A

16

2WT-B

N/A

16

1100/D

N/A

20

1151

B401/B110LP/B116LP

16/16/1

1400

N/A

20

1451

B401B / B406B

16/ 1

1451DH

DH-400

16

1800

N/A

N/A

1851B

B101B

N/A

1851B

B107B

N/A

1851DH

DH1851DC

16

2100/D/S

N/A

16

2100T/D/S

N/A

16

2151

B401/B110LP/B116LP

16/16/1

2300T

N/A

16

2400

N/A

16

2400AIT

N/A

1

2400AT

N/A

1

2400TH

N/A

16

2451

B401B / B406B

16/1

2451

DH-400

16

2451TH

B401B / B406B

16/1

2800

N/A

N/A

2800TH

N/A

N/A

2851B

B101B

N/A

2851B

B107B

N/A

2851BTH

B101B

N/A

2851BTH

B107B

N/A

2851DH

DH2851DC

16

DH100P

N/A

16

DH100LP

N/A

16

2WTA-B

N/A

1

2WTA-RB

N/A

1