2 special application dc power output connections, 3 relays - programmable – System Sensor PDRP-2001 User Manual

Page 27

Advertising
background image

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

27

Output Circuits

Installation

2.4.2 Special Application DC Power Output Connections

Special Application Resettable and Nonresettable 24 VDC power is available on the PDRP-2001
control panel.

2.4.3 Relays - Programmable

The PDRP-2001 control panel provides a factory default programmed alarm relay, fail-safe trouble
relay and supervisory relay. Each relay can be programmed to activate for other conditions (refer
to “On-Board Relays” on page 65). Each Form-C relay is rated for 2 amps @ 30VDC (resistive)
and 0.5 amps @ 30 VAC (resistive).

Note that relay connections must be power-limited.

Figure 2.8 Special Application Auxiliary Power

Special Application

4-Wire Smoke Detector Power (500 mA)

24 VDC filtered, resettable power for 4-wire smoke detectors

can be obtained from these terminals (power-limited)

Special Application

Resettable or Nonresettable Power (500 mA)

24 VDC filtered, resettable or nonresettable power

can be obtained from these terminals (power-limited)

• Jumper JP31 pins 1 & 2 for nonresettable power

(as illustrated in figure to right)

• Jumper JP31 pins 2 & 3 for resettable power

ms

-1

0

UDt

b9

.c

dr

-

+

-

+

4

3

2

1

Figure 2.9 Relay Terminals

Note: Relay contacts are shown with
power applied to the panel and no active
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay
which will transfer on any trouble or total
power failure.

ms1

0

ud

relay.

cdr

Advertising