Output map zone 1 4 – System Sensor PDRP-2001 User Manual

Page 54

Advertising
background image

54

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

Programming

Master Programming Level

Output Circuit Map

Output Mapping (per input zone) allows the programmer/operator to assign the Output Circuits that
will be activated when a particular Input Zone or cross-zoned releasing group goes active. Pressing
1 for Output Circuit Map while viewing Edit Input Zone Screen #3 will display screens which show
the Output Circuits programmed to activate when the selected Input Zone (or cross-zoned releasing
group) is activated. Output Map Screen #1 displays the Output Type Codes and programming for
Output Circuits 1 through 3 and Output Map Screen #2 displays the Output Type Code and
programming for Output Circuit 4.

As an example, if Template 1 has been selected as the FACP Configuration [refer to“FACP
CONFIG (Application Templates)” on page 51], sel
ecting the Output Circuit Map for Input Zone 1
will display the following screens:

The screens indicate that when Input Zone 1 is activated:

Output Circuit #1 default programmed as Alarm NAC will activate (Yes)
Output Circuit #2 default programmed as
Output Circuit #3 default programmed as Release 1 will activate (Yes)
Output Circuit #4 default programmed as

Note that the MAP may indicate that an Input Zone is programmed to a particular Output Circuit
but, if it is cross-zoned with one or more other Input Zones, all must be active in order to activate
the Output Circuit. Refer to the examples in “Circuit Mapping and Cross-Zoning” on page 104.

The Output Circuit Map can be customized by selecting or deselecting any of the four output
circuits for activation. Pressing the number key corresponding to the selected output will toggle the
display between Yes for activation by the Input Zone to No for no activation. The new customized
programming is automatically saved by the panel as soon as it is entered.

Freeze Supervision

Pressing 2 for Freeze Supervision while viewing Edit Input Zone Screen #3, will program the
FACP to supervise the devices connected to the selected zone for a temperature freeze condition.
Each press of the 2 key will toggle the display between Freeze Supv. Yes and No. The factory
default setting is No Freeze Supervision.

INPUT ZONE #

1=OUTPUT CIRCUIT MAP
2=FREEZE SUPV.

Edit Input Zone Screen #3

OUTPUT MAP ZONE 1
1=ALARM NAC YES
2= NAC
3=RELEASE 1 YES

Output Map Screen#1

OUTPUT MAP ZONE 1
4=

Output Zone Screen#2

Advertising