PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

135

NAC Wiring

Wire Requirements

F.1 NAC Wiring

The following table lists NAC wiring requirements for the FACP.

Calculations are based on Direct-Current Resistance data for uncoated copper wire, per

National Electrical Code (2005 Edition) Table 8, Conductor Properties.

NAC

Load

(Amps)

Max.

allowable
total loop

resistance

(ohms)

CLASS-B

Max. allowable wire pair length

(feet)

CLASS-A

Max. allowable wire pair length

(feet)

AWG 12

solid

AWG 14

solid

AWG 16

solid

AWG 18

solid

AWG 12

solid

AWG 14

solid

AWG 16

solid

AWG 18

solid

0.25

13.60

3523

2215

1391

875

1762

1107

695

438

0.5

6.80

1762

1107

695

438

881

554

348

219

0.75

4.53

1174

738

464

292

587

369

232

146

1

3.40

881

554

348

219

440

277

174

109

1.25

2.72

705

443

278

175

352

221

139

88

1.5

2.27

587

369

232

146

294

185

116

73

1.75

1.94

503

316

199

125

252

158

99

63

2

1.70

440

277

174

109

220

138

87

55

2.25

1.51

391

246

155

97

196

123

77

49

2.5

1.36

352

221

139

88

176

111

70

44

2.75

1.24

320

201

126

80

160

101

63

40

3

1.13

294

185

116

73

147

92

58

36

Table F.2 NAC Wiring Requirements for FACP