PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

23

Operating Power

Installation

provided with overcurrent protection and may not contain any power disconnect devices. A
separate Earth Ground connection must be made to ensure proper panel operation and lightning and
transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm

2

)] to the

grounding stud in the backbox and then run the wire to TB1. Do not use conduit for the Earth
Ground connection since this does not provide reliable protection.

Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J12 on the main circuit
board using the plug-in connector and cable provided. The battery charger is current-limited and
capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.

!

WARNING: BATTERY CONTAINS SULFURIC ACID
BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN
AND EYES AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID,
IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK
IMMEDIATE MEDICAL ATTENTION.

TB6

SW1

Figure 2.4 Operating Power Connections

120 VAC Power

Hot (L1)

Ground

Neutral (L2)

Ground Stud

J12