System Sensor PDRP-2001 User Manual

Page 125

Advertising
background image

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

125

NFPA Standard-Specific Requirements

The following figure illustrates an example of Central Station/Remote Station Reporting using a
411UD. The relay contacts from the PDRP-2001 may be used to trip any dialer UL-listed for
Central Station/Remote Station Reporting Services.

Figure C.1 FACP Connection to 411UD

Channel1

Channel 2

Channel 3

Channel 4 (2.2K ELR)

Relay Output (DACT Trouble) from 411UD

FACP Supervisory Relay

FACP Alarm Relay

FACP Trouble Relay

J4 Not Installed

411UD

1

2

3

4

5

6

7

8

+ 24 VDC nonresettable

- 24 VDC nonresettable power

2.2K ELRs P/N 27070

1

2

3

4

5

6

7

8

9

1 2 3 4 5 6 7

FACP

Jumper -VDC to Trouble Relay contact

Trouble Input

(nonsupervised
, power-limited)