Trouble reminder, Charger disable, Canadian option – System Sensor PDRP-2001 User Manual

Page 72: Trouble reminder charger disable canadian option

Advertising
background image

72

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

Programming

Master Programming Level

Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between
Enabled Yes and Enabled No. The control panel will automatically update the time for daylight
savings time when Enabled Yes is selected.

Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the
programmer to select the month that daylight savings time will begin. In this sub-screen, pressing
1 will select March, 2 will select April, and 3 will select May.

Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will begin. In the first sub-
screen, pressing 1 will select the first week, 2 will select the second week, and 3 will select the third
week, while in the second sub-screen, pressing 1 will select the fourth week and 2 will select the
last week of the selected month.

Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the
programmer to select the month that daylight savings time will end. In this sub-screen, pressing 1
will select September, 2 will select October, and 3 will select November.

Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will end. In the first sub-
screen, pressing 1 will select the first week, 2 will select the second week, and 3 will select the third
week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will select the
last week of the selected month.

Trouble Reminder

The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for
alarms and troubles, after the panel has been silenced. Refer to “System Setup” on page 66, for a
detailed description of this feature. Pressing 2 while viewing System Setup Screen #2 will cause
the display to toggle to Trouble Remind Yes, which enables this feature. Each press of the 2 key
will cause the display to toggle between Trouble Remind Yes and Trouble Remind No.

Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for more
than 24 hours will cause the FACP to resound the trouble sounder.

Charger Disable

Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or disable
the onboard battery charger. If an external battery charger is being used, the onboard battery
charger must be disabled. Each press of the 3 key will toggle between Chargr Disable No and
Chargr Disable Yes.

Canadian Option

Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with
Canadian requirements. The display will change to Canadian Opt. On. Each press of the 2 key
will cause the display to toggle between Canadian Opt. On and Canadian Opt. Off. The factory
default setting is Canadian Opt. Off.

The Canadian Options configures the FACP with the following as required by Canada:

The following zone type codes are not available:

non-latching supervisory

non-latching drill

Any allowed zone type programmed as Auto-Resettable will be changed to latching version of
that zone type (N.O. Contact AR will be changed to N.O. Contact, Combo with AR
Supervisory will be changed to Combo, 2-wire Heat AR will be changed to 2-wire Heat, Low
Pressure AR will be changed to Low Pressure, High Pressure AR will change to High Pressure
and Supervisory AR will change to Supervisory)

The auto-silence feature can be enabled or disabled. If this feature is enabled, the alarm signals
will be turned off after 20 minutes of activation

SYSTEM SETUP

1=TIME-DATE
2=TROUBLE REMIND
3=CHARGR DISABLE

System Setup Screen #2