System Sensor PDRP-2001 User Manual

Page 120

Advertising
background image

120

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

FACP Configuration Templates

Template 6: Single Hazard - 2 Zones Cross-Zoned With All Active

B.6 Template 6: Single Hazard - 2 Zones Cross-Zoned With

All Active

Table Legend:

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).

Cx = cross-zone where x is the number of the Release Solenoid. All inputs with the same Release
Solenoid number must be active at the same time to turn on the corresponding solenoid output
circuit

Input Zone Types:

Zone 1 = 2-wire smoke

Zone 2 = Fire

Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)

Zone 4 = Manual Release

Zone 5 = Pull Station

Zone 6 = Low Pressure

Output Circuit Types:

Output 1 = Alarm NAC, silenceable, coded for steady on

Output 2 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10
secs.), silenceable, coded for steady on

Output 3 = Supervisory Bell NAC, silenceable, coded for steady on

Output 4 = Release Solenoid 1 (unsupervised for shorts)

Timers

Soak Timer 1 - set for 10 minutes

Soak Timer 2 - set for 10 minutes

Waterflow Delay Timer - set for 10 seconds

AC Loss Delay Timer - set for 2 hours

Operation

Activation of both Input Zone 1 (2-Wire Smoke) and Zone 2 (Fire) at the same time, or Zone
4 (Manual Release) or Zone 5 (Pull Station) will operate the Release Solenoid 1 Output #4.
Release Solenoid will turn off water release following time-out of the 10 minute Soak Timer 1.
Activation of any one of these zones will operate Alarm NAC Output #1

Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is a
10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10 seconds

Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3

Template 6: SINGLE HAZARD - 2 ZONES CROSS-ZONES WITH ALL ACTIVE

INPUT ZONES

1

2

3

4

5

6

OUTPUT CIRCUITS

2-WIRE SMOKE

FIRE

WATERFLOW

MANUAL

RELEASE

PULL

STATION

LOW

PRESS.

#1 ALARM NAC

X

X

X

X

#2 WATERFLOW NAC

X

#3 SUPV. BELL NAC

X

#4 RELEASE SOLENOID 1

C1

C1

X

X

Advertising