Working with the ApplicationTemplate

Mapping the actual machine structure in the »PLC Designer«

42

Lenze · ApplicationTemplate · 1.3 EN - 04/2013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3. Allocate unique designations to the slaves inserted

(example: "L_94_HL_ActuatorSpeed").
The names can be selected freely and must …

• only contain the characters "A ... Z", "a ... z", "0 ... 9", or "_";
• not start with a digit.

You can enter a name by clicking the element.
Example:

4. Setting the cycle time

• The value for the EtherCAT master cycle time has to be defined according to the cycle

time of the quickest task.

• The

icon in front of the respective device indicates the successful

EtherCAT communication.

Note: The EtherCAT cycle time is to be set to the quickest task cycle time set. In this

ApplicationTemplate, the quickest task cycle time is set to 2 ms, therefore 2000 μs have to

be set here.