Rockwell Automation 1302 575v AC Drive - Canada Only User Manual

Page 23

Advertising
background image

3–5

1302 Preinstallation

Publication 1302-5.0 — January, 1998

Table 3.B - Recommended Power Wire Sizes

Type of Wiring

Terminals

Size of Wire

(maximum)*

AC Input Power

R(L1), S(L2), T(L3)

14 AWG, 2 (mm

2

)

Output Power

U(T1), V(T2), W(T3)

14 AWG, 2 (mm

2

)

DC Bus

ć , +

14 AWG, 2 (mm

2

)

Snubber Resistor

+10 VDC, 10 COM

14 AWG, 2 (mm

2

)

Ground

GND

14 AWG, 2 (mm

2

)

Table 3.C - Recommended Power Terminal Tightening Torque

Drives

Terminals

Maximum Tightening Torque

All

All power wires

1.08 NewtonĆmeters (9.5 inĆlb)

Recommended Control and Signal Wire Sizes

Table 3.D shows the recommended wire sizes to connect I/O signals
to the terminal strip on the Regulator board. The minimum wire
insulation rating is 600V. Operator controls can be up to 303 meters
(1000 feet) from the 1302 Drive. All signal wires should be
twisted-pair.

Table 3.D - Recommended Control and Signal Wire Sizes and Tightening Torque

Drives Terminals

Minimum

Wire Size

Maximum

Wire Size

Maximum

Tightening Torque

All

1ć16

20 AWG, 0.5 (mm

2

)

14 AWG, 2 (mm

2

)

0.5 NewtonĆmeters

(4.5 inĆlb)