FĆ00 Control Source Select

This parameter selects the Drive

control source and speed

reference source.

Parameter Range:

Default Setting:

Step Size:

0 = Local control; control signals and

speed reference from the keypad

1 = Remote control; control signals from

the terminal strip; speed reference

from the analog input

2 = Remote control; control signals from

the terminal strip; speed reference

from the keypad

3 = Remote control; control signals from

the terminal strip; multiĆspeed presets

from the terminal strip

0 = Local control

N/A

When FĆ00 = 0, the Drive responds to sequencing commands (start, stop, forward, reverse) from only

the keypad.

When FĆ00 = 1, 2, or 3, the Drive responds to sequencing commands from the terminal strip. Note that

the drive will respond to the stop command from the keypad regardless of the value in this parameter.

Refer to the FĆ23 to FĆ25 MultiĆSpeed Presets parameter description for more information about

multiĆspeed presets.