9–3

Troubleshooting

Publication 1302-5.0 — January, 1998

= HIGH BUS VOLTAGE

The DC bus is charged above the electronic trip threshold. Note that the fault will not clear until the bus falls

below the high bus level.

Possible Cause

Corrective Action

The deceleration rate setting in FĆ02 is too fast.

Decrease the deceleration rate in FĆ02. Refer to

chapter 8 for the FĆ02 parameter description.
Install the optional snubber resistor braking kit.

The Drive was started into a forwardĆrunning load

that has a high inertia.

Install the optional snubber resistor braking kit.

High input line.

Verify that the AC input is within specification. Install

an isolation transformer if required.

= LOW BUS VOLTAGE

The DC bus voltage has fallen below the electronic trip low threshold level. Note that the fault will not clear

until the linput line voltage is within the proper range. This may take a few seconds.
Important: If a line dip or momentary power loss occurs and the DC bus is able to rise back to the proper

level within 500 ms, the Drive will automatically restart (if the Drive was running when the fault

occurred).

Possible Cause

Corrective Action

Loss of input power.

Check incoming power.

Low line voltage.

Check incoming power. Install an isolation

transformer if required.