FĆ04 Maximum Speed

This parameter limits the speed

reference to the Drive.

Regardless of what speed

reference is supplied, the

regulator will not command a

speed greater than the value in

FĆ04.

Parameter Range:

Default Setting:

Step Size:

30 to 240 Hz

60 Hz

0.10 Hz if FĆ04

<

100 Hz

0.25 Hz if FĆ04

100 Hz

!

ATTENTION: The user is responsible for ensuring that driven machinery, all driveĆtrain

mechanisms, and process line material are capable of safe operation at maximum speed

(FĆ04). Failure to observe this precaution could result in bodily injury or equipment damage.

FĆ05 Current Limit

This parameter limits motor

output torque while it is running

or accelerating.

Parameter Range:

Default Setting:

Step Size:

10% to 150% of rated drive current

150%

1.0%

When output current attempts to exceed the preset current limit, motor current will be maintained or

reduced, or the acceleration / deceleration time will be extended. If current limit is set too low or too high

relative to the required load, an overcurrent fault may occur (OC will be displayed).