8–11

Programming

Publication 1302-5.0 — January, 1998

FĆ12 Remote Reference Offset

This parameter scales the

remote speed reference (0 to

10VDC or 0 to 20 mA) to a

minimum value.

Parameter Range:

Default Setting:

Step Size:

0% to 40% of full scale minimum reference

0%

0.10%

Typically, the value of the minimum speed reference (the amount of reference at minimum speed, FĆ03) is

either 0 VDC or 0 mA. Enter the parameter value as a percentage of the full scale reference to be offset from

minimum speed.

To calculate the scaled minimum reference, use the following equation:

Desired Minimum Speed Offset

Reference Range

100 + %offset

Scaling Examples

Example 1: If the remote analog input speed reference is 0 to 20 mA (J6 set on terminals 2 and 3), and

the available analog reference signal is 4 to 20 mA, use FĆ12 to obtain minimum speed with minimum

analog input as follows:

Example 2: If the remote analog input speed reference is 0 to 10 VDC (J6 set on terminals 1 and 2), and

the available signal is offset 0.4 VDC, use FĆ12 to obtain minimum speed with minimum analog input as

follows:

4

20 x 100 = 20% offset

0.4

10 x 100 = 4% offset

FĆ13 Percent Selected Speed Reference Display Enable

This parameter enables or

disables the fourth monitor

mode display.

Parameter Range:

Default Setting:

Step Size:

ON = Fourth monitor mode display is

enabled.

OFF = Fourth monitor mode display is

disabled.

OFF

N/A

If FĆ13 = ON, the current value of the active speed reference can be displayed by pressing the

Mode
Enter

key

(while the Drive is running) until all three monitor mode LEDs are on. The active speed reference is

displayed as 1 to 100% of maximum speed (FĆ04).

If FĆ13 = OFF, the active speed reference will not be displayed.

Refer to Chapter 3 for more information on the monitor mode displays.