3–6

1302 Preinstallation

Publication 1302-5.0 — January, 1998

Recommended Motor Lead Lengths

The following motor lead lengths are recommended to reduce line
disturbances and noise. See Figure 3.3.

For applications using one motor, motor lead length should not

exceed 76 meters (250 feet).

For applications with multiple motors, total motor lead length should

not exceed 76 meters (250 feet).

When total lead length exceeds 76 meters (250 feet), nuisance trips can
occur, caused by capacitive current flow to ground. Note that these
capacitively-coupled currents should be taken into consideration when
working in areas where drives are running. If the motor lead length
must exceed these limits, the addition of output line reactors or other
steps must be taken to correct the problem. See Table 3.E. Note that
the motor lead lengths shown in Table 3.E are only guidelines. Your
application may be restricted to a shorter motor lead length due to:

The type of wire

The placement of the wire (for example, in conduit or a cable tray)

The type of line reactor (For example, with or without LC filters)

The type of motor

Figure 3.3
How to Measure Motor Lead Lengths

1302 Drive

Motor

38m (125')

38m (125')

15m (50')

61m (200')

61m (200')

8m (25')

8m (25')

76m (250')

Motor

Motor

Motor

Motor

Motor

Motor

1302 Drive

1302 Drive

1302 Drive

All examples represent 76m (250') of motor lead length.